AFE adopts Infineon as the core inverter and adopts full digital control. It has high control precision, fast response speed, high precision, high reliability, programmable features and automatic two-way operation function.
The function of the energy feedback unit is to feed back the regenerative energy generated in the process of motor speed regulation to the power grid, so as to avoid the energy loss caused by the resistance heating of the conventional energy consumption braking unit, so as to achieve considerable energy saving effect. The product is mainly for motor testing, access to the DC bus in the test platform, power to the inverter, and has two-way energy conversion function.
The altitude shall not exceed 2000m (more than 2000m, derating is required). No medium with explosion risk, no gas or conductive medium that corrodes metal and damages insulation, no water vapor and serious mold are allowed
Equipment interface:
The schematic picture is as follows:
Interface introduction
The equipment interface has three interfaces: RS232 \rs485 \ Ethernet;
1. RS232 is responsible for real-time communication with the lower computer control board for data acquisition;
Communication protocol internal customization;
2. RS485 interface is connected with remote equipment for remote control, and the equipment address can be set; Communication setting: 9600, N, 8,1; The communication protocol is standard Modbus protocol;
3. Ethernet interface is connected with remote equipment for remote control, and IP can be set;
Touch screen mode control description
1. touch screen bit MODBUS server mode
2. to be filled in correctly
Local IP address 192.168.1.102
Local port number 3000
Remote IP address 192.168.1.100
Remote port number 3000
***********************************************************
The following is a detailed explanation of the agreement
***********************************************************
PCS Communication checklist:
ADD | Read / write type | Register contents | describe | Note |
0 | R | Grid A phase voltage | V, No decimal | |
1 | R | Grid A phase current | A, No decimal | |
2 | R | Grid B phase voltage | V, No decimal | |
3 | R | Grid B phase current | A, No decimal | |
4 | R | Grid C phase voltage | V, No decimal | |
5 | R | Grid C phase current | A, No decimal | |
6 | R | Grid frequency | Hz, With one decimal | |
7 | R | DC voltage | V, no signed no decimal | |
8 | R | DC current | A, No decimal | |
9 | R | Error code | See Appendix for codes | |
10 | R | Start stop sign | 1=start 0=stop | |
11 | R | Reserve | ||
12 | W | Start stop | 1=start 0=stop |
Error code description:
No. | Error code | Error definition | Note |
1 | 1 | DC overvoltage | |
2 | 2 | DC under voltage | |
3 | 3 | A Overvoltage | |
4 | 4 | A under voltage | |
5 | 5 | B Overvoltage | |
6 | 6 | B under voltage | |
7 | 7 | C Overvoltage | |
8 | 8 | C under voltage | |
9 | 9 | Frequency error | |
19 | 10 | A over current | |
11 | 11 | B over current | |
12 | 12 | C over current | |
13 | 13 | Emergency stop | |
14 | 14 | Over heat | |
15 | 15 | Current limiting protection | |
16 | 16 | ||
17 | 17 | IGBT protection | |
18 | 18 | DC overvoltage - hardware | |
19 | 19 | System error | |
20 | 20 | Remote stop | |
21 | 21 | Reference error | |
22 | 22 | Phase sequence error |